Click through to view more products

FireMaster

FireMaster is an uninsulated active fire curtain barrier that vertically protects openings in fire rated walls or can be used to completely replace non-load bearing fire rated walls. To protect means of escape or where there are combustibles in close proximity see FireMaster Plus.

FireMaster Fire Curtains are designed as barriers to prevent the spread of fire in accordance with AS1530.4.

firemaster

Barrier Construction

Each roller is up to 5m wide with multiple roller construction up to 30m wide. Wide Single Roller (WSR) construction is available up to 17m wide.

Material Finish

Metalwork is zinc coated mild steel. This can be painted on site or powder coated to DULUX or RAL colours.

Operation

A 24v electromagnetic brake holds the fire curtain open. Closing is by gravity at a controlled speed of 0.06 – 0.15m/s. Opening is driven my one or more 24vDC tubular motors mounted within the barrel.

Test / Reset

Test is performed by a simple key switch operator. The system is reset manually by pressing the reset button on the control panel. Automatic reset is available.

Fabric

The curtain material is a satin weave fibreglass fabric with a silver polyurethane coating on both sides and integral stainless steel wire. It is 0.54mm thick, and weighs approximately 690g/m² in its finished form.

Fire Rating

Up to 4 hours fire integrity to AS1530.4. Assessment report EXOVA EWFA-RIR-21553.

Incident Irradiance (kW/m2)

Time (mins) I0– 0mm I1,000– 1,000mm
0 0.00 0.00
15 16.32 12.00
30 23.12 17.00
60 32.64 24.00
120 48.97 36.00


Bottom Bar

Standard bottom bar is Jumbo which is a triangular shaped bar 40mm wide. Also available is the ‘T’ bar and operable ceiling interface systems (SLAT) in 150mm and 75mm profiles.

Click through to view more products