Get In Touch

    ×
    Get A Free Quote

    Get a Quote

    • Contact Details

      Please provide the information below so we are able to provide you with more accurate pricing.
    • Product Selection*

      Please select your desired products from the lists below
    • Please include sizes and required Fire Ratings
    ×
    Book Now

    CPD Training Booking

    FireMaster Plus

    • Fire Rating: – / 120 / -
    • Max Width :30 Metres
    • Max Height:7.5 Metres

    The FireMaster Plus partially insulated Fire Curtain is a revolutionary product within the fire engineering industry. The FireMaster Plus Fire Curtain incorporates a unique intumescent fabric that was developed and produced by Coopers Fire. It uses a unique rapid reaction graphite flake which expands to over 20 times its original thickness on exposure to heat and fire, creating an partially insulated carbon barrier to heat. FireMaster Plus partially insulated fire curtain reduces radiant heat to under 2.5 kilowatts per square meter for over 15 minutes. You can escape safely just a few inches away from a 600°C fire. For our non-insulated fire curtain please see our FireMaster.

    INSULATED FIRE CURTAIN CONSTRUCTION

    Single roller construction only. Each roller is up to 30 meters wide and has a minimum of 70mm diameter with a wall thickness of no less than 1.5mm. Rollers wider than 4 meters are wide single rollers incorporating Wide Single Roller (WSR) head-boxing. Metalwork is zinc coated mild steel. This can be painted on site or powder coated to DULUX or RAL colours.

    OPERATION

    FireMaster Plus will remain retracted within its head box until it is automatically activated by the fire alarm signal. Once activated it will completely close the opening, creating a fire and smoke compartment. When activated, deployment is by gravity at a controlled speed of 0.06 – 0.15m/s. Thus making this is the only true gravity fail-safe product on the market. Testing is performed by a simple key switch. It is reset manually by pressing a reset button on the control panel. Automatic reset is available.

    FIRE RATING

    Full scale and full assembly fire testing to AS1530.4 providing fire integrity of 2 hours with low radiant heat. Insulation was achieved for 2 hours When measured 50mm from the curtain. Testing also includes motor testing and proving 12 operating cycles across 30 minutes fire exposure. No need to fire protect the headbox or side guides as the complete product is fire rated. Assessment report EXOVA EWFA-RIR-22049. Incident Irradiance (kW/m2)

    BOTTOM BAR

    The standard bottom bar is Jumbo which is a triangular shaped bar 40mm wide. Also available is the ‘T’ bar and operable ceiling interface systems (SLAT) in 150mm and 75mm profiles.

    Benefits

    • Provides an equivalent FRL of -/120/- when the insulation requirement is measured 50mm from the fire curtain
    • Does not require sprinklers or drenchers to reduce heat
    • Can be used near combustibles and means of egress where insulated barriers are normally used. Pending fire engineered solution

    Learn More

    For Further Reference please read the documents provided below. If you wish to obtain further information regarding our Fire Attenuation Screens, please contact us at (02) 9526 3100, or email us at sales@greenefire.com.au